APPENDIX B

 

Suggested initial retest frequency for Portable Appliance Testing

--------------------------------------------------------------------------------
Construction Sites 110 or 240volt equipment:

Class 1: Formal visual: Monthly: Full Test: 3 Monthly

Class 2: Formal visual: Monthly: Full Test: 3 Monthly

--------------------------------------------------------------------------------

Industrial (Including kitchens)

Stationary and IT Class 1: Formal visual: Annually* Full Test: Annually

Stationary Equipment Class 2: Formal Visual: Annually Full Test: 2 yearly

--------------------------------------------------------------------------------

Offices and Shops

Class 1: Formal Visual: Annually* Full Test: 1 - 2 Years

Class 2: Formal Visual: Annually Full Test: Not Required

--------------------------------------------------------------------------------

Hotels

Class 1: Formal Visual: Annually* Full Test: 1 - 2 Years

Class 2: Formal Visual: Annually Full Test: Not Required

--------------------------------------------------------------------------------

Schools

Class 1: Formal Visual: Annually** Full Test: Annually

Class2: Formal Visual: Annually** Full Test 2 Years

--------------------------------------------------------------------------------

Areas or Equipment to which the Public have access

Class 1: Formal Visual: 3 Monthly Full Test: Annually

Class 2: Formal Visual: 3 Monthly Full Test: 2 Years

--------------------------------------------------------------------------------

Notes: * = Frequency should be reduced to 6 monthly for hand-held appliances

** = Frequency should be reduced to 3 Monthly for hand-held Appliances